Product

Product Clean-room, Hospital Room, Lab, Special Lab

Lab controller

NLC 100D (Duplicated LAB Environment Controller) is consisted of two dualized boards as it assures the hot-standby function for labs, operating room and other industrial environment control most widely required for the stability of the environment system, and it is the product with automatic switchover when there is any malfunction by having the dualization in CPU, power, all input and output point, communication and others.

System configuration
Main characteristics
  • The tap controller has the dual structure for all I/O point and communication
  • It is structured in 6 analogs in input [RTD, Air Flow, current input 4] and 3 analog outputs [voltage], digital input, and 2 digital outputs
  • Air valve control for independent operation [Stand alone]
  • General input and output for flexible control operation
  • Built-in flexible algorithm following the indoor environment control purpose
  • Built-in air flowing sensor for appropriate wind volume measurement
  • Damper auto control following ventilation frequency
  • Damper auto control following the pressure difference
  • Valve on/off control following temperature
  • Monitoring and control through the central monitoring system
  • Monitoring for any malfunction with I/O point or more and board switchover if communication is malfunctioning

Exclusive controller for operation room

NORC 10/11/12/13/14
Operating Room Controller

High reliability under the critical environment
The clean room air circulation system is the exclusive controller for operating room, lab and others with FFU (Fan Filter Unit), BFU (Blower Filter Unit) and variable wind volume control device in VAV (Variable Air Volume) Unit.

System configuration
Main characteristics
  • 4-20mA current input or 0-10V voltage input up to 4 channels (connected to temperature/humidity sensor and pressure sensor)
  • Input 1 channel of RTD (Pt 1000) for -50℃~150℃
  • 4 channels of dry contact input contact point
  • 2 channels of 200-240VAC/3A Triac output (for cooling and heating coil control)
  • 3 channels of RS485 (upper communication and FAN/HMI equipment for communication)
  • Input of 200-240VAC/60Hz
  • Scope of o3 temperature -10 ℃~50℃
  • Refer to the product catalog for detailed specification

Low oxygen chamber (environment chamber)

The low pressure/low oxygen chamber is a special facility to build up specific high level environment through adjusting the environment condition as in oxygen, nitrogen density, air pressure and others.

Main characteristics
  • High plane copy environment control chamber of world best specification
  • - Building up of high level environment : 0 ~ 6,000m
    - Building up of low pressure environment : Atmospheric pressure ~ 350mmHg
    - Wind control : 50 ~ 120L/Min ±1.0%
  • Chamber frame to endure 760 torr of outside and 300 torr of inside
  • A system with nitrogen that may building up to 6,000m for plane pressure and low oxygen environment
  • CO2 reducing and removal system to maintain the CO2 density to be 1,000 ppm or less when training
  • interface through the mobile equipment (smart phone, pad) (limited to permitted users only)
  • Maximizing the system safety through the control system dualization
  • Alarm system on abnormal situation of temperature, humidity, pressure, or oxygen density
  • Power breakdown prepared system (UPS, small power generator and etc)
  • Access control and CCTV system linkage
  • Available for integrated operation of human calorie meter chamber

Human calorie meter chamber (Metabolic chamber)

The human calorie meter chamber is a special facility to calculate the energy consumption volume by measuring and analyzing the oxygen volume and carbon dioxide volume consumed by users in the chamber.

Main characteristics
  • Human meta-bolic chamber optimized for measurement analysis
  • - Temperature : 15℃∼30℃ ±0.1℃
    - Humidity : 40%∼60% ±1.5%
    - Wind control : 50 ~ 120L/Min ±1.0%
  • Blood Hole is available to collect blood from outside users in human metabolic chamber
  • Accurate mass analysis (nitrogen, oxygen, carbon dioxide, degree of analysis 0.002%)
  • Measure and analyze the gas density in the chamber with 5 – 60 sec interval (Epoch)and calculate the energy consumption volume
  • Applying various energy consumption volume analysis algorithm
  • Interface through the mobile equipment (smart phone, pad) (limited to permitted users only)
  • Maximizing the system safety through the control system dualization
  • Alarm system on abnormal situation of temperature, humidity, pressure, or oxygen density
  • Power breakdown prepared system (UPS, small power generator and etc)
  • Access control and CCTV system linkage
  • Available for integrated operation of low pressure/low oxygen chamber